WTW BW-18 Boiler Treatment
General Information: BW-18
reacts with the oxygen found in feed water to form a chemical compound, thus
tying up free oxygen. By
deactivating free oxygen, BW-18 prevents the localized oxygen-induced corrosion
known as oxygen pitting. BW-18
contains polymers to provide sludge conditioning as well.
Usage Information: BW-18 meets the
requirements of the F.D.A. as set forth in CFR Title 21, Part 173, Subpart D,
Section 173.310 and is U.S.D.A. G-6 authorized.
Injection/Feeding: BW-18 should be fed continuously by an automated system proportionate to
boiler feedwater. BW-18 is compatible with the other components used in a
complete water treatment program.
Product Properties: Physical
state: dark red to brown
pH full strength: 12.1
Solubility: miscible
in all proportions
Density: 9.1 lbs./gal.
Handling Information: BW-18 can be
handled in accordance with the Material Safety Data Sheet.
Keep container tightly closed when not dispensing chemical
Packaging and Shipping: Available in
plastic containers. All containers are
non-returnable. F.O.B. Cloverdale, Indiana.
|
Boiler Treatment Products |
| Product |
Initial Amount |
Test Method |
Test Frequency |
Test Values |
| BW-18 |
20-30
oz. Per 100 HP-Day
|
Test
for
Sulfite |
Daily |
30
- 60 ppm
|
WTW Technical
Library: Bulletin
BW-18
©1998 Water Treatment Warehouse, Inc.
Cloverdale, IN
|