WTW BW-19 Boiler Treatment
General Information: BW-19
is a catalyzed, liquid, Super Oxygen Scavenger designed to removed free oxygen
from boiler systems. WTW BW-19 is
often used as a supplemental oxygen scavenger, but also finds application as a
stand alone oxygen scavenger. BW-19
is designed to prevent oxygen pitting when used properly.
Usage Information: BW-19 is not
U.S.D.A. authorized. Please contact
WTW for assistance with U.S.D.A. applications.
Injection/Feeding: BW-19 is most often fed on a continuous basis.
This is the recommended method.
Product Properties: Physical
state: almost colorless
pH full strength: 7.2
Solubility: miscible
in all proportions
Density: 10 lbs./gal.
Handling Information: BW-19 can be
handled in accordance with the Material Safety Data Sheet.
Keep container tightly closed when not dispensing chemical
Packaging and Shipping: Available in
plastic containers. All containers are
non-returnable. F.O.B. Cloverdale, Indiana.
|
Boiler Treatment Products |
| Product |
Initial Amount |
Test Method |
Test Frequency |
Test Values |
| BW-19 |
Will
be dictated by the amount of oxygen entering the boiler through the feed
water system.
|
Test
for
Sulfite |
Daily |
30
- 60 ppm
|
WTW Technical
Library: Bulletin
BW-19
©1998 Water Treatment Warehouse, Inc.