WTW RL-24 Return Line Treatment
General Information: RL-24
is a neutralizing amine product designed to proved corrosion protection in
condensate systems.
Usage Information: RL-24 meets the
requirements of the F.D.A. as set forth in CFR Title 21, Part 173, Subpart D,
Section 173.310 and is U.S.D.A. G-6 authorized.
Injection/Feeding: RL-24 should be fed via a continuous system on a proportional basis.
It should be fed directly into the steam distribution system or fed into
the boiler as part of a mixture with boiler chemicals
Product Properties: Physical
state: colorless-light amber
pH: 11.6
Solubility: Miscible in all proportions
Density: 8.2
lbs./per gal.
Handling Information: RL-24 can be
handled in accordance with the Material Safety Data Sheet.
Keep container tightly closed when not dispensing chemical
Packaging and Shipping: Available in
plastic containers. All containers are
non-returnable. F.O.B. Cloverdale, Indiana.
|
Return Line Treatment Products |
| Product |
Initial Amount |
Test Method |
Test Frequency |
Test Values |
| RL-24 |
Proportional
|
pH
|
Daily |
7.8
- 8.4
|
WTW Technical
Library: Bulletin RL-24
©1998 Water Treatment Warehouse, Inc.